Projects:Modbus Meter

From Wiki
The printable version is no longer supported and may have rendering errors. Please update your browser bookmarks and please use the default browser print function instead.

Hardware

Communication

  • Send (HEX)
    • 01 : Address
    • 04 : Function
    • 00 : Starting address high
    • 00 : Starting address low
    • 00 : Number of points high
    • 00 : Number of points low
    • 71 : Error check high
    • CB : Error check low
  • Receive (HEX)
    • 01 : Address
    • 04 : Function
    • 04 : number of bytes
    • 43 : data high - high
    • 66 : data high - low
    • 33 : data low - high
    • 34 : data low - low
    • 1B : Error check high
    • 38 : Error check low
  • Return data according to IEEE 754 float point format